Replaced 17 year old boiler due to cracked and holed cast iron cells and leaking water onto burners when running. Cell’s originally cracked due to little or no water while burner running. Replaced boiler, added 2nd low water cut off as added protection for boiler. The original Hartford loop was too shallow causing boiler to hold roughly 1 gallon of water instead of 2-3 gallons minimum. Maintenance is also key in preventing something like this happening.